TLX Matrix Switch SNMP Traps Manual 10 Rev. E - July, 2015
Low RX Power Warning Begin and Clear
An SFP module has the ability to monitor and trigger an alarm on a high or low RX laser power reading.
This ability is internal to the SFP and is part of the digital diagnostic interface common to many SFPs. This
notification is sent when bit 6 of byte 117 in the real-time diagnostic registers changes from 0 to 1 (Begin) or
from a 1 to a 0 (Clear).
This bit is set when the SFP received laser power falls below the low power warning level. The SFP RX
power value is stored at bytes 104 & 105 of the SFP diagnostic register table.
Begin OID: 1,3,6,1,4,1,17658,2,2,2,0,39
Clear OID: 1,3,6,1,4,1,17658,2,2,2,0,40
Objects:
1: sfpLabel
2: sfpTemperature
3: sfpThresholdLowRxPowerWarning
4: sysContact
5: sysDescr
6: sysLocation
7: sysName